MECHANICAL COMPLIANCE SUMMARY
2021 WSEC Compliance Forms for Commercial Buildings including Group R1, R2, and Group R3 & R4 over 3 stories Administered by: ©2021 NEEA, All rights reserved
Project & Applicant
Information
Project Title Ridgefield Dugouts - 2021 WSEC For Building Department Use: Date:      Apr 9, 2025
Project Address 230 Pioneer Street
Ridgefield, WA 98642
Applicant Name Jaren Koistinen
Applicant Phone 360-606-8449
Applicant Email jaren@alpineengineers.com

Mechanical Compliance Summary Scope - Compliance verification provided in this report is limited to code minimum efficiency requirements for mechanical equipment types defined in Tables C403.3.2(1) through C403.3.2(16) of the 2021 WSEC-C. This includes efficiency multipliers for economizer exceptions. Performance criteria for additional energy efficiency and load management measures ARE NOT included in this report. Additional documentation is required to demonstrate compliance with all other provisions of the energy code, including better than code efficiency criteria for Section C406. For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com.

General Occupancy All Commercial General Building Use Type(s) Office, Other
Building Cond. Floor Area 3,195
General Project Types
New Building
New Building
or Addition
Mechanical Scope
Single Zone Systems & Equipment
Alteration
Mechanical Scope
Project Cond. Floor Area 3,195
Floors Above Grade 1
Overall Compliance Path General Prescriptive
Mechanical Project Description
Batting Cages for the City of Ridgefield. The Umpire Room is 400 SF and is conditioned. The two large Batting Cage rooms are unconditioned spaces.
Mechanical Compliance
Scope and Method
Project Type Mechanical Scope Economizer Exception(s)
Applied?
DOAS Ventilation
Provided?
Equipment Efficiency
Compliance Verification
New Building Single Zone Systems & Equipment Yes Yes COMPLIES
Additional Energy Efficiency
Measures (AEM)
  HVAC heating equipment - 5-20% better than code efficiency
High performance dedicated outside air systems (DOAS)
Load Management Measures
(LDM)
    No mechanical load management measures included in project
Does building include occupancy classifications requiring DOAS? Yes Does project include DOAS equipment? Yes
Based on project scope do TSPR requirements apply? No Do all systems comply with Appendix D standard reference design or qualify for an exception to TSPR? No
Scope & Space Conditioning New Building - Single Zone Systems & Equipment Compliance Verification Complies
Single Zone Air Systems Category - Heat pump, split & single package, SC, SDHV
Air Systems Summary Information
System/Equip ID Quantity
of Items
Supply Airflow
Control
Ventilation Standard Ventilation CFM
(Total if Multiple
Items)
Ventilation
Air Source
Paired with DOAS Ventilation energy recovery Energy Recovery
Efficiency (%)
HP-1 Constant volume IMC Ventilation Separate DOAS ERV-1 Provided but not required 60
Air Systems & Equipment - Cooling
System/
Equip ID
Cooling System/Equip Type Specific Type Cooling Capacity
per item (Btu/h)
Econo Exception
Multipliers
(Full/IPLV)
Required Cooling
Efficiency
(Code Min + Econo)
Required Part
Load Efficiency
(Code Min + Econo)
Proposed Cooling
Efficiency
CE
Units
Proposed Part
Load Efficiency
PL
Units
Efficiency Compliance
Verification
HP-1 Heat pump, air cooled Split system 6,000 0 0 13.4 0 15 SEER2 IEER COMPLIES
Air Systems & Equipment - Heating
System
/Equip ID
Heating System/Equip Type Specific Type Heat Pump
Heating Capacity
per item (Btu/h)
Cooling Capacity
per Item (Btu/h)
(Identical to
Cooling Table)
Required Heat Pump
Heating Efficiency
Required
Low OSA
Temp Efficiency
Proposed Heat Pump
Heating Efficiency
HPH
Units
Proposed
Low OSA
Temp Efficiency
LTH
Units
Efficiency Compliance
Verification
HP-1 Heat pump, air cooled, heating Split system 8,700 6,000 7.5 0 10.9 HSPF2 COP COMPLIES
Air Systems & Equipment Details
System/Equip ID Discrete Area(s) Served Location In Project Documents - Plan/Detail # System/Equip Compliance Path
HP-1 Umpire Room M1.1 M2.1 General Prescriptive
  WSEC Equip Efficiency Reference Table - Cooling: Table C403.3.2(2) Unitary Heat Pumps  
  Economizer Compliance Method: Economizer not required Heating Section/Auxiliary Heating Type: Electric resistance (or None)
  WSEC Equip Efficiency Reference Table - Heating: Table C403.3.2(2) - Unitary Heat Pumps  
  LTH Units: COP  
  Proposed Low OSA Temp Efficiency: