Project & Applicant Information |
Project Title | Wesley Bradley Park Phase 2 - Care Center - 2021 WSEC | For Building Department Use: Date: Dec 6, 2024 |
---|---|---|---|
Project Address | 707 39th Ave. SE Puyallup, WA 98374 |
||
Applicant Name | Jill Krance | ||
Applicant Phone | 952-252-4822 | ||
Applicant Email | jill.krance@INSITEARCHITECT.COM |
Mechanical Compliance Summary Scope - Compliance verification provided in this report is limited to code minimum efficiency requirements for mechanical equipment types defined in Tables C403.3.2(1) through C403.3.2(16) of the 2021 WSEC-C. This includes efficiency multipliers for economizer exceptions. Performance criteria for additional energy efficiency and load management measures ARE NOT included in this report. Additional documentation is required to demonstrate compliance with all other provisions of the energy code, including better than code efficiency criteria for Section C406. For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com.
General Occupancy | All Commercial | General Building Use Type(s) |
Healthcare, Senior Care Community |
Building Cond. Floor Area | 37,315 | ||
---|---|---|---|---|---|---|---|
General Project Types |
New Building
|
New Building or Addition Mechanical Scope |
Central Plant Systems
Single Zone Systems & Equipment
Multiple Zone Systems & Equipment
|
Alteration Mechanical Scope |
Project Cond. Floor Area | 37,315 | |
Floors Above Grade | 1 | ||||||
Overall Compliance Path |
General Prescriptive |
||||||
Mechanical Project Description |
VRF System for heating and cooling with two DOAS with ERV to provide ventilation air.
|
Mechanical Compliance Scope and Method |
||||||
---|---|---|---|---|---|---|
Project Type | Mechanical Scope | Economizer Exception(s) Applied? |
DOAS Ventilation Provided? |
Equipment Efficiency Compliance Verification |
||
Building Addition | Central Plant Systems | Yes | NA | COMPLIES | ||
New Building | Single Zone Systems & Equipment | Yes | Yes | COMPLIES | ||
New Building | Multiple Zone Systems & Equipment | No | Yes | COMPLIES | ||
Additional Energy Efficiency Measures (AEM) |
No mechanical additional energy efficiency measures included in project | Load Management Measures (LDM) |
HVAC load management |
|||
Does building include occupancy classifications requiring DOAS? | Yes | Does project include DOAS equipment? | Yes | |||
Based on project scope do TSPR requirements apply? | No | Do all systems comply with Appendix D standard reference design or qualify for an exception to TSPR? | Yes |
Scope & Space Conditioning | Building Addition - Central Plant Systems | Compliance Verification | Complies |
---|
VRF Multi-Split Systems Category - Heat pump outdoor unit |
---|
Cooling Equipment Efficiency Information | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
System ID | Cooling System Type | Specific Type | Cooling Capacity (Btu/h) |
Econo Exception Multipliers (Full/IPLV) |
Required Full Load Efficiency (Code Min + Econo) |
Required Part Load Efficiency (Code Min + Econo) |
Proposed Cooling Efficiency |
CE Units | Proposed Part Load Efficiency |
PL Units |
Efficiency Compliance Verification |
|||
CU-1,2,3,4 | VRF air-cooled HP | Heat pump w/ heat recovery | 216,000 | 0 | 0 | 10.4 | 13.7 | 12.7 | EER | 20.5 | IEER | COMPLIES |
Heating Equipment Efficiency Information | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
System ID | Heating System Type | Specific Type | Heat Pump Heating Capacity (Btu/h) |
Cooling Capacity (Btu/h) (Identical to Cooling Table) |
Required Heat Pump Heating Efficiency |
Required Low Water Temp Efficiency |
Proposed Heat Pump Heating Efficiency |
HE Units | Proposed Low Water Temp Efficiency |
LWTH Units |
Efficiency Compliance Verification |
Equipment Details | |||||||||
---|---|---|---|---|---|---|---|---|---|
System ID | Location in Project Documents - Plan/Detail # | Quantity of Fan Coil Units in VRF System | System/Equip Compliance Path | ||||||
CU-1,2,3,4 | M2.0A, M2.1B, ME1.1 | 60 | General Prescriptive | ||||||
WSEC Equipment Efficiency Reference Table: Table C403.3.2(9) VRF Air-to-Air & Water Source Heat Pumps | Air-side economizer exception applied?: Exp 1 - DOAS paired with cooling system (Note equip location limitations) | ||||||||
Economizer Compliance Method: Economizer not required |
Scope & Space Conditioning | New Building - Single Zone Systems & Equipment | Compliance Verification | Complies |
---|
Single Zone Air Systems Category - Fan coil unit, hydronic & VRF |
---|
Air Systems Summary Information | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
System/Equip ID | Quantity of Items |
Supply Airflow Control |
Ventilation Standard | Ventilation CFM (Total if Multiple Items) |
Ventilation Air Source |
Paired with DOAS | |||||
FC-1, 3, 7, 8, 9, 10, 11, 21 | 8 | Constant volume | ASHRAE Standard 62.1 | 1045 | Other System | ||||||
FC-12, 19, 20 | 3 | Constant volume | ASHRAE Standard 62.1 | 350 | Other System | ||||||
FC-13, 15, 17, 18, 22 | 5 | Constant volume | ASHRAE Standard 62.1 | 905 | Other System | ||||||
FC-2, 14, 16 | 3 | Constant volume | ASHRAE Standard 62.1 | 700 | Other System | ||||||
FC-4 | Constant volume | ASHRAE Standard 62.1 | 65 | Other System | |||||||
FC-5, 6, 24, 25 | 4 | Constant volume | ASHRAE Standard 62.1 | 470 | Other System | ||||||
FC-A | 32 | Constant volume | ASHRAE Standard 62.1 | 2720 | Other System | ||||||
FC-B, FC-23 | 5 | Constant volume | ASHRAE Standard 62.1 | 285 | Other System |
Air Systems & Equipment - Cooling | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
System/ Equip ID |
Cooling System/Equip Type | Specific Type | Cooling Capacity per item (Btu/h) |
||||||||
FC-1, 3, 7, 8, 9, 10, 11, 21 | Fan coils, hydronic & VRF, cooling | VRF | 24,000 | ||||||||
FC-2, 14, 16 | Fan coils, hydronic & VRF, cooling | VRF | 30,000 | ||||||||
FC-4 | Fan coils, hydronic & VRF, cooling | VRF | 9,000 | ||||||||
FC-5, 6, 24, 25 | Fan coils, hydronic & VRF, cooling | VRF | 12,000 | ||||||||
FC-12, 19, 20 | Fan coils, hydronic & VRF, cooling | VRF | 18,000 | ||||||||
FC-13, 15, 17, 18, 22 | Fan coils, hydronic & VRF, cooling | VRF | 36,000 | ||||||||
FC-A | Fan coils, hydronic & VRF, cooling | VRF | 8,000 | ||||||||
FC-B, FC-23 | Fan coils, hydronic & VRF, cooling | VRF | 6,000 |
Air Systems & Equipment - Heating | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
System /Equip ID |
Heating System/Equip Type | Specific Type | Heating Output Capacity per item (Btu/h) |
||||||||
FC-1, 3, 7, 8, 9, 10, 11, 21 | Fan coils, hydronic & VRF, heating | VRF | 27,000 | ||||||||
FC-2, 14, 16 | Fan coils, hydronic & VRF, heating | VRF | 34,000 | ||||||||
FC-4 | Fan coils, hydronic & VRF, heating | VRF | 9,000 | ||||||||
FC-5, 6, 24, 25 | Fan coils, hydronic & VRF, heating | VRF | 13,000 | ||||||||
FC-12, 19, 20 | Fan coils, hydronic & VRF, heating | VRF | 13,000 | ||||||||
FC-13, 15, 17, 18, 22 | Fan coils, hydronic & VRF, heating | VRF | 40,000 | ||||||||
FC-A | Fan coils, hydronic & VRF, heating | VRF | 9,000 | ||||||||
FC-B, FC-23 | Fan coils, hydronic & VRF, heating | VRF | 6,700 |
Air Systems & Equipment Details | |||||||||
---|---|---|---|---|---|---|---|---|---|
System/Equip ID | Discrete Area(s) Served | Location In Project Documents - Plan/Detail # | System/Equip Compliance Path | ||||||
FC-1, 3, 7, 8, 9, 10, 11, 21 | Office, Education, Dayroom, Corridors, Conf Room, Nurse | M2.0A, M2.1A, M2.2A, ME1.1 | General Prescriptive | ||||||
Cooling Capacity Source: CU-1, 2, 3, 4 | |||||||||
Heating Capacity Source: CU-1, 2, 3, 4 | |||||||||
FC-12, 19, 20 | Spa, Office, Director | M2.1A, M2.2B, ME1.1 | General Prescriptive | ||||||
Cooling Capacity Source: CU-1, 2, 3, 4 | |||||||||
Heating Capacity Source: CU-1, 2, 3, 4 | |||||||||
FC-13, 15, 17, 18, 22 | Serving Kitchen, Dining, Chapel, Commons, Dayroom | M2.1A, M2.2B, M3.2, ME1.1 | General Prescriptive | ||||||
Cooling Capacity Source: CU-1, 2, 3, 4 | |||||||||
Heating Capacity Source: CU-1, 2, 3, 4 | |||||||||
FC-2, 14, 16 | Staff Breakroom, Therapy | M2.0A, M2.1A, M2.2A, ME1.1 | General Prescriptive | ||||||
Cooling Capacity Source: CU-1, 2, 3, 4 | |||||||||
Heating Capacity Source: CU-1, 2, 3, 4 | |||||||||
FC-4 | Med Records | M2.0A, ME1.1 | General Prescriptive | ||||||
Cooling Capacity Source: CU-1, 2, 3, 4 | |||||||||
Heating Capacity Source: CU-1, 2, 3, 4 | |||||||||
FC-5, 6, 24, 25 | Storage, Corridor, Laundry | M2.0A, ME1.1 | General Prescriptive | ||||||
Cooling Capacity Source: CU-1, 2, 3, 4 | |||||||||
Heating Capacity Source: CU-1, 2, 3, 4 | |||||||||
FC-A | Units | M2.1A, M2.2B, M3.0, ME1.1 | General Prescriptive | ||||||
Cooling Capacity Source: CU-1, 2, 3, 4 | |||||||||
Heating Capacity Source: CU-1, 2, 3, 4 | |||||||||
FC-B, FC-23 | Units, Office | M2.2B, M3.0, ME1.1 | General Prescriptive | ||||||
Cooling Capacity Source: CU-1, 2, 3, 4 | |||||||||
Heating Capacity Source: CU-1, 2, 3, 4 |
Single Zone Air Systems Category - Heat pump, split & single package, SC, SDHV |
---|
Air Systems Summary Information | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
System/Equip ID | Quantity of Items |
Supply Airflow Control |
Ventilation Standard | Ventilation CFM (Total if Multiple Items) |
Ventilation Air Source |
Paired with DOAS | Ventilation energy recovery | Energy Recovery Efficiency (%) |
|||
DHU-1 | Staged volume | ASHRAE Standard 62.1 | 1400 | Integral | Not provided, not required |
Air Systems & Equipment - Cooling | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
System/ Equip ID |
Cooling System/Equip Type | Specific Type | Cooling Capacity per item (Btu/h) |
Econo Exception Multipliers (Full/IPLV) |
Required Cooling Efficiency (Code Min + Econo) |
Required Part Load Efficiency (Code Min + Econo) |
Proposed Cooling Efficiency |
CE Units |
Proposed Part Load Efficiency |
PL Units |
Efficiency Compliance Verification |
|
DHU-1 | Heat pump, air cooled | Split system | 120,000 | 0 | 0 | 11.0 | 13.9 | 13 | EER | 16 | IEER | COMPLIES |
Air Systems & Equipment - Heating | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
System /Equip ID |
Heating System/Equip Type | Specific Type | Heat Pump Heating Capacity per item (Btu/h) |
Cooling Capacity per Item (Btu/h) (Identical to Cooling Table) |
Required Heat Pump Heating Efficiency |
Required Low OSA Temp Efficiency |
Proposed Heat Pump Heating Efficiency |
HPH Units |
Proposed Low OSA Temp Efficiency |
LTH Units |
Efficiency Compliance Verification |
DHU-1 | Heat pump, air cooled, heating | Split system | 124,000 | 120,000 | 3.4 | 2.25 | 3.7 | COP | 2.4 | COP | COMPLIES |
Air Systems & Equipment Details | |||||||||
---|---|---|---|---|---|---|---|---|---|
System/Equip ID | Discrete Area(s) Served | Location In Project Documents - Plan/Detail # | System/Equip Compliance Path | ||||||
DHU-1 | Pool | M2.1A, ME1.1 | General Prescriptive | ||||||
Heating Section/Auxiliary Heating Type: Electric resistance (or None) | Economizer Compliance Method: Air-side economizer provided | ||||||||
WSEC Equip Efficiency Reference Table - Cooling: Table C403.3.2(2) Unitary Heat Pumps | |||||||||
Proposed Low OSA Temp Efficiency: 2.4 | LTH Units: COP | ||||||||
WSEC Equip Efficiency Reference Table - Heating: Table C403.3.2(2) - Unitary Heat Pumps |
Single Zone Equipment Category - Baseboard & wall heaters |
---|
Radiant & Passive Convection Information | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
System/Equip ID | Quantity of Items |
Ventilation Standard | Ventilation CFM (Total if Multiple Items) |
Ventilation Air Source |
Paired with DOAS | ||||||
ERH-A | 2 | ASHRAE Standard 62.1 | 0 | Other System | |||||||
FF-A | 4 | ASHRAE Standard 62.1 | 0 | Other System |
Radiant & Passive Convection Equipment - Heating | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
System /Equip ID |
Heating System/Equip Type | Specific Type | Heating Output Capacity per Item |
HC Units | |||||||
FF-A | Wall heaters | Electric | 3,000 | Watts | |||||||
ERH-A | Wall heaters | Electric | 750 | Watts |
Equipment Details | |||||||||
---|---|---|---|---|---|---|---|---|---|
System/Equip ID | Discrete Area(s) Served | Location In Project Documents - Plan/Detail # | System/Equip Compliance Path |
Scope & Space Conditioning | New Building - Multiple Zone Systems & Equipment | Compliance Verification | Complies |
---|